Installing the pipes
Install the drain fitting and the drain hose (for model with heat pump only)
Condensation is produced and flows from the outdoor unit when the appliance is operating in the heating
mode. In order not to disturb neighbours and to respect the environment, install a drain fitting and a drain
hose to channel the condensate water. Install the drain fitting and rubber washer on the outdoor unit chassis
and connect a drain hose to it as shown in the figure.
Use suitable connecting pipes and equipment for the refrigerant R410a.
The connecting pipes must not exceed the maximum lengths 10 m.
Wrap all the refrigerant pipes and joints.
Tighten the connections using two wrenches working in opposite directions.
INSTALLATION DIMENSION DIAGRAM
The installation must be done by trained and qualified service personnel with reliability according to this
manual.
• Contact service centre before installation to avoid the malfunction due to unprofessional installation.
• When picking up and moving the units, you must be guided by trained and qualified person.
• Ensure that the recommended space is left around the appliance.
Bleeding
Humid air left inside the refrigerant circuit can cause
compressor malfunction. After having connected the indoor and
outdoor units, bleed the air and humidity from the refrigerant
circuit using a vacuum pump.
1.
Unscrew and remove the caps from the 2-way and 3-way
valves.
2.
Unscrew and remove the cap from the service valve.
3.
Connect the vacuum pump hose to the service valve.
4.
Operate the vacuum pump for 10-15 minutes until an
absolute vacuum of 10 mm Hg has been reached.
5.
With the vacuum pump still in operation, close the low-
pressure knob on the vacuum pump coupling. Stop the
vacuum pump.
6.
Open the 2-way valve by 1/4 turn and then close it after
10 seconds. Check all the joints for leaks using liquid soap or
an electronic leak device.
7.
Turn the body of the 2-way and 3-way valves. Disconnect
the vacuum pump hose.
8.
Replace and tighten all the caps on the valves.
Diameter
(mm)
Twisting moment
(Nm)
Ø 6 15~20
Ø 9.5 35~40
Ø 12 45~50
Ø 16 60~65
Ø 19 70~75
Conversion joint
12K MODE:
Refrigerant fluid direction of flow
INDOOR
UNIT
Vacuum pump
2-way valve
Service
inlet
Connect to the
indoor unit
(6) Open by 1/4 turn
Valve cap
(2) Turn
(8) Secure
(2) Turn
(8) Secure
(7) Turn to open fully
(7) Turn to open fully
3-way valve
(2) Turn
(8) Secure